HAP carrier 6.4 infiltrations and fresh air
- upvotes
- 4
- comments
- 8
Post
Hi everyone! I recently started using HAP 6.4 and have a couple of questions for more experienced users. First, how do you handle infiltration for heating and cooling load calculations? I found typical values of around 0.2–0.6 ACH, depending on building airtightness, but without a blower door test it seems difficult to choose a realistic value. What method or assumptions do you normally use? Second, do you use HAP to determine the required fresh/outdoor air, or do you calculate it separately and then input the airflow into HAP? Also, if anyone has a sample HAP model for a warehouse with office areas that they would be willing to share, that would be very helpful. I mainly want to check whether I’m setting up my model and inputs correctly. Thank you!
Extracted from these lines
[comment u/SANcapITY] For OA - never use HAP for a VAV system - it never gets it right. Do it yourself and plug it back in.
[comment u/Lazy-Rain-7375] I never use HAPs values for outside air. I calculate that separately in excel, or have a junior do it to expose them to the codes in a simpler calculation.
[comment u/Intrepid_Cattle5008] I'd let HAP size the outdoor air. Give each space an ASHRAE 62.1 space usage so it defaults the per person and per area rates