A fire alarm technician reports failure across 3 out of 4 Honeywell HPFF12 power supplies where charger circuits failed and batteries went flat without registering trouble alerts.

Source: Autobound Signal API · 125 signals tracked for Honeywell · updated

Get Honeywell's live signals in Claude or ChatGPT, or by API

AskWhat changed at Honeywell this week? Use Autobound signals for honeywell.com.

What happened

Post: "Honeywell HPFF12 charger"

Source

RedditNov 13, 2026By u/ImpendingTurnip

r/firealarms

Honeywell HPFF12 charger

upvotes
4
comments
21

Post

Highlighted: the lines this signal was extracted from

I have 4 HPFF12 power supplies in a building controlling sounder bases and horn strobes. They are all setup the same. 3 out of 4 have no charger voltage and batteries are flat. There are no troubles on the FACP or the power supply. All of the charger jumpers are on correctly, fuses are good however I have no voltage. Only 1 is reporting battery troubles correctly. I’m assuming I have 3 bad power supplies. Anyone else have any suggestions?

reddit.com/r/firealarms/comments/1xvm60j/honeywell_hpff12_chargerRead the full source

Comments on the post

5 of 21 comments
  • “I hate B200S sounder bases. Probably failed if the charger circuit isn't outputting at all, and the batteries would not be flat if they were being charged.”

    u/Simple-Row-54622 points · Nov 13, 2026View

  • “On other Honeywell power supplies (FCPS-24, PSE-10) only the aux trouble contacts will change state on a battery trouble, if you are only monitoring the input/output the control module won't see an open circuit as those contacts only open on an output trouble. Not sure if these HPF are the same but see if the one that does correctly show a trouble for the battery is wired the same as the others th”

    u/zynx332 points · Nov 13, 2026View

  • “Monitor the trouble relay?”

    u/FlynnLives3D1 points · Nov 14, 2026View

  • “How are they configured? If you have aux power jumped to one of the inputs to keep the output active, the charger will not work.”

    u/Gamer_06271 points · Nov 13, 2026View

  • “I had one a couple of months ago that was all normal would even report troubles but I would not activate on alarm, ended up buying a new one from RYBB, I had a couple dozen of them failed in similar fashion as you’re describing over the last 10 years so what you’re describing is not uncommon, time to replace or upgrade”

    u/Makusafe1 points · Nov 14, 2026View

Extracted by Autobound

From the Signal API record
Signal
Customer feedback

What this signalsUser posts often show product pain before it reaches reviews or churn.

Subreddit
r/firealarms
Event date
Nov 2026

The full record

From the Signal API record

Numbers

Mentions
2

Details

Timing
Ongoing state
Category
Reliability
Virality
Medium
Post kind
Text
Prominence
Core
Company's role
Vendor

Topics and mentions

Topics

  • fire alarm
  • hardware reliability
  • power supplies

Flair

  • Technical Support:snoo sad:

Products named

  • HPFF12

Extraction

Sentiment
Negative
Detected
Nov 13, 2026
signal_type
reddit-company
signal_subtype
customerFeedback

Use this data

Get every Reddit signal for Honeywell and the companies you sell to, in the tools you already use.

  1. Ask Claude about it

    Connect Autobound to Claude, Claude Code or Cursor with MCP. Then ask: “What changed at Honeywell this week?”

  2. Send it to your own tools

    The Signal API returns Reddit signals for any list of companies as JSON, for your CRM, warehouse or app.

  3. Try it free

    Sign up and spend your free credits on the companies you sell to.

    Start Free1,000 free credits

The API returns more than this page shows

This page shows a preview. The full reddit-company record in the Signal API and MCP can also have these 8 fields. Some fields are empty for some signals.

Company

  • linkedin_urlValue in the API
  • industriesValue in the API
  • employee_count_lowValue in the API
  • employee_count_highValue in the API
  • revenueValue in the API
  • descriptionValue in the API

Signal

  • signal_nameValue in the API
  • associationValue in the API
Show the full JSONThe record on this page and the API request

GET /v1/signals/1d5d91b2-6904-5179-aad3-204a8e5628f4 returns this record as JSON. POST /v1/companies/enrich returns every signal for honeywell.com.

{
  "signal_id": "1d5d91b2-6904-5179-aad3-204a8e5628f4",
  "signal_type": "reddit-company",
  "signal_subtype": "customerFeedback",
  "detected_at": "2026-11-13T22:45:11+00:00",
  "company": {
    "name": "Honeywell",
    "domain": "honeywell.com"
  },
  "data": {
    "nsfw": false,
    "stage": "none",
    "awards": 0,
    "timing": "ongoing_state",
    "topics": [
      "fire alarm",
      "hardware reliability",
      "power supplies"
    ],
    "post_id": "1xvm60j",
    "summary": "A fire alarm technician reports failure across 3 out of 4 Honeywell HPFF12 power supplies where charger circuits failed and batteries went flat without registering trouble alerts.",
    "category": "reliability",
    "comments": [
      {
        "url": "https://www.reddit.com/r/firealarms/comments/1xvm60j/comment/19slg0qgqr1sw/",
        "depth": 0,
        "score": 2,
        "author": "Simple-Row-5462",
        "excerpt": "I hate B200S sounder bases.\n\n Probably failed if the charger circuit isn't outputting at all, and the batteries would not be flat if they were being charged.",
        "posted_at": "2026-11-13T22:53:40.000Z",
        "author_url": "https://www.reddit.com/user/Simple-Row-5462/"
      },
      {
        "url": "https://www.reddit.com/r/firealarms/comments/1xvm60j/comment/19slht97cgcmb/",
        "depth": 0,
        "score": 2,
        "author": "zynx33",
        "excerpt": "On other Honeywell power supplies (FCPS-24, PSE-10) only the aux trouble contacts will change state on a battery trouble, if you are only monitoring the input/output the control module won't see an open circuit as those contacts only open on an output trouble. Not sure if these HPF are the same but see if the one that does correctly show a trouble for the battery is wired the same as the others th",
        "posted_at": "2026-11-13T23:33:51.000Z",
        "author_url": "https://www.reddit.com/user/zynx33/"
      },
      {
        "url": "https://www.reddit.com/r/firealarms/comments/1xvm60j/comment/19slkv5ecjj6s/",
        "depth": 0,
        "score": 1,
        "author": "FlynnLives3D",
        "excerpt": "Monitor the trouble relay?",
        "posted_at": "2026-11-14T00:42:17.000Z",
        "author_url": "https://www.reddit.com/user/FlynnLives3D/"
      },
      {
        "url": "https://www.reddit.com/r/firealarms/comments/1xvm60j/comment/19slgjyplheck/",
        "depth": 0,
        "score": 1,
        "author": "Gamer_0627",
        "excerpt": "How are they configured?\n\n If you have aux power jumped to one of the inputs to keep the output active, the charger will not work.",
        "posted_at": "2026-11-13T23:05:39.000Z",
        "author_url": "https://www.reddit.com/user/Gamer_0627/"
      },
      {
        "url": "https://www.reddit.com/r/firealarms/comments/1xvm60j/comment/19slnlv58bbog/",
        "depth": 0,
        "score": 1,
        "author": "Makusafe",
        "excerpt": "I had one a couple of months ago that was all normal would even report troubles but I would not activate on alarm, ended up buying a new one from RYBB, I had a couple dozen of them failed in similar fashion as you’re describing over the last 10 years so what you’re describing is not uncommon, time to replace or upgrade",
        "posted_at": "2026-11-14T01:43:46.000Z",
        "author_url": "https://www.reddit.com/user/Makusafe/"
      },
      {
        "url": "https://www.reddit.com/r/firealarms/comments/1xvm60j/comment/19smg3j96cnhh/",
        "depth": 0,
        "score": 1,
        "author": "Electronic-Concept98",
        "excerpt": "Its HONEYWELL! it is crap",
        "posted_at": "2026-11-14T12:22:32.000Z",
        "author_url": "https://www.reddit.com/user/Electronic-Concept98/"
      },
      {
        "url": "https://www.reddit.com/r/firealarms/comments/1xvm60j/comment/19smkhe8t8f6o/",
        "depth": 0,
        "score": 1,
        "author": "rapturedjesus",
        "excerpt": "I'm in the middle of a case with Honeywell on HPFF8CMs, we have 12 on a critical DoE site that experiences frequent AC shutdowns, half of these power supplies randomly started latching troubles requiring a dump or a PS reset to clear. They replaced 2 under RMA for this in the first 6 months and are now claiming theyve never heard of any problems with fault handling on them, even after they receive",
        "posted_at": "2026-11-14T14:00:51.000Z",
        "author_url": "https://www.reddit.com/user/rapturedjesus/"
      },
      {
        "url": "https://www.reddit.com/r/firealarms/comments/1xvm60j/comment/19sn22kug3g0w/",
        "depth": 0,
        "score": 1,
        "author": "Odd-Act-4355",
        "excerpt": "Were these power supplies allowed to \"die\" while on battery backup? Some equipment gets really squirrelly if this happens. Some will also not charge if the battery voltage gets too low. Verify the proper startup and shutdown procedures. Cycle the p/s thru a few proper startup and shutdowns (with good batteries). They might recover.\n\n We had a similar situation once. We replaced the dead panel twic",
        "posted_at": "2026-11-14T20:35:11.000Z",
        "author_url": "https://www.reddit.com/user/Odd-Act-4355/"
      }
    ],
    "evidence": [
      "[post] I have 4 HPFF12 power supplies in a building controlling sounder bases and horn strobes. They are all setup the same. 3 out of 4 have no charger voltage and batteries are flat.",
      "[post] All of the charger jumpers are on correctly, fuses are good however I have no voltage. Only 1 is reporting battery troubles correctly. I’m assuming I have 3 bad power supplies."
    ],
    "virality": "medium",
    "post_date": "2026-11-13T22:45:11.000Z",
    "post_kind": "text",
    "post_text": "I have 4 HPFF12 power supplies in a building controlling sounder bases and horn strobes. They are all setup the same. 3 out of 4 have no charger voltage and batteries are flat. There are no troubles on the FACP or the power supply. All of the charger jumpers are on correctly, fuses are good however I have no voltage. Only 1 is reporting battery troubles correctly. I’m assuming I have 3 bad power supplies. Anyone else have any suggestions?",
    "sentiment": "negative",
    "subreddit": "firealarms",
    "event_date": "2026-11",
    "post_flair": [
      "Technical Support:snoo_sad:"
    ],
    "post_title": "Honeywell HPFF12 charger",
    "prominence": "core",
    "source_url": "https://www.reddit.com/r/firealarms/comments/1xvm60j/honeywell_hpff12_charger/",
    "entity_role": "vendor",
    "post_author": "ImpendingTurnip",
    "upvote_ratio": 1,
    "mention_count": 2,
    "mention_surge": false,
    "subreddit_url": "https://www.reddit.com/r/firealarms/",
    "total_upvotes": 4,
    "comments_total": 21,
    "total_comments": 21,
    "post_author_url": "https://www.reddit.com/user/ImpendingTurnip/",
    "signal_category": "feedback",
    "comments_included": 8,
    "products_mentioned": [
      "HPFF12"
    ]
  }
}

Long text fields are shortened on this page.

Looking up one signal by its id is free. Enrich costs 2 credits per signal returned; a call with no results is free.