Carrier RTU/ Open Bacnet card
- upvotes
- 4
- comments
- 9
Post
Highlighted: the lines this signal was extracted from
After getting these cards, it seems we have to build our own 10 wire whip that essentially controls the main boards outputs like a t-stat. If we want additional information we have to run seperate sensors for DAT, OAT, and enthalpy. Is there a better option or is this what it is? At least trane has a board built in and we can pull everything it see's into tridium.
Also quoted as evidence
[comment u/Fr33PantsForAll] RTU open is a junk product made by the worst major player in the industry. What you should be doing is using a programable controller from anyone else.
[comment u/TanneriteStuffedDog] Had to check if you were one of my guys, we’re fighting two Carrier RTUs with RTU open boards... You can either integrate with bacnet, which FORCES a 5° minimum heat/cool setpoint difference that can only be changed with a Carrier service too