A building automation technician reports configuration and lag difficulties interfacing Johnson Controls PCG1610 controllers with new 2-10VDC modulating valves.

Source: Autobound Signal API · 69 signals tracked for Johnson Controls · updated

Get Johnson Controls' live signals in Claude or ChatGPT, or by API

AskWhat changed at Johnson Controls this week? Use Autobound signals for johnsoncontrols.com.

What happened

Post: "JCI PCG Controllers Question"

Source

RedditOct 29, 2026By u/Zerobeat50125

r/BuildingAutomation

JCI PCG Controllers Question

upvotes
3
comments
21

Post

Highlighted: the lines this signal was extracted from

Greetings! I have a site with several PCG1610 controllers, utilizing analog modulating valves for the heating and cooling. Recently, all of the valves were changed out with new Belimo valves and operators. The problem experienced, is the original valves were 0-10vdc, while the new valves are 2-10vdc. This is causing lag issues when calls for heating and cooling are placed. There is no option for 2-10vdc in the setup, and modifying the output for 19% minimum out does not help, it does not increase above 2vdc until the call exceeds 25%. Has anyone run into this before, and if so, what did you do to work around it? Thanks, appreciate any and all assistance!

reddit.com/r/BuildingAutomation/comments/1xiozmn/jci_pcg_controllers_...Read the full source

Comments on the post

5 of 21 comments
  • “Are you changing the Min Value or Min Output Value? It needs to be Min Output Value to scale it properly if I recall correctly”

    u/hhhhnnngg3 points · Oct 29, 2026View

  • “It can be changed in PCT. I can post a picture later if that helps”

    u/Disastrous-Lemon82763 points · Oct 29, 2026View

  • “there is definitely an option to change it to 2-10 in pct/cct, probably a way to get to it in mct, and definitely with mel if you can bring it back from the dead with .net framework workarounds.”

    u/Battlewaxxe3 points · Oct 29, 2026View

  • “Are they Belimo -MFT actuators? If so, you can program them for 0–10VDC using the Belimo ZTH programmer. Also, it sounds like you have access to CCT? If so, you can open the .caf file and adjust the hardware output range from 0–100% to 20–100%. It sounds like you already tried something similar by setting the minimum to 19%, which is the right idea. Just make sure you're making that adjustment in”

    u/JREControls2 points · Oct 29, 2026View

  • “You should have 2-10, but also you can setup a scale with 20 as the low output and 100 as the high output.”

    u/cbytes10012 points · Oct 30, 2026View

Extracted by Autobound

From the Signal API record
Signal
Customer feedback

What this signalsUser posts often show product pain before it reaches reviews or churn.

Subreddit
r/BuildingAutomation
Event date
Oct 2026

Companies

  • BelimoAlso named

The full record

From the Signal API record

Numbers

Mentions
3

Details

Timing
Ongoing state
Category
Features
Virality
Medium
Post kind
Text
Prominence
Core
Company's role
Vendor

Topics and mentions

Topics

  • building automation
  • configuration
  • hvac

Products named

  • PCG1610
  • CCT
  • PCT

Extraction

Sentiment
Negative
Detected
Oct 29, 2026
signal_type
reddit-company
signal_subtype
customerFeedback

Use this data

Get every Reddit signal for Johnson Controls and the companies you sell to, in the tools you already use.

  1. Ask Claude about it

    Connect Autobound to Claude, Claude Code or Cursor with MCP. Then ask: “What changed at Johnson Controls this week?”

  2. Send it to your own tools

    The Signal API returns Reddit signals for any list of companies as JSON, for your CRM, warehouse or app.

  3. Try it free

    Sign up and spend your free credits on the companies you sell to.

    Start Free1,000 free credits

The API returns more than this page shows

This page shows a preview. The full reddit-company record in the Signal API and MCP can also have these 8 fields. Some fields are empty for some signals.

Company

  • linkedin_urlValue in the API
  • industriesValue in the API
  • employee_count_lowValue in the API
  • employee_count_highValue in the API
  • revenueValue in the API
  • descriptionValue in the API

Signal

  • signal_nameValue in the API
  • associationValue in the API
Show the full JSONThe record on this page and the API request

GET /v1/signals/6fc8f03b-008e-509b-a0ca-ce3b70f95dff returns this record as JSON. POST /v1/companies/enrich returns every signal for johnsoncontrols.com.

{
  "signal_id": "6fc8f03b-008e-509b-a0ca-ce3b70f95dff",
  "signal_type": "reddit-company",
  "signal_subtype": "customerFeedback",
  "detected_at": "2026-10-29T16:36:59+00:00",
  "company": {
    "name": "Johnson Controls",
    "domain": "johnsoncontrols.com"
  },
  "data": {
    "nsfw": false,
    "stage": "none",
    "awards": 0,
    "timing": "ongoing_state",
    "topics": [
      "hvac",
      "building automation",
      "configuration"
    ],
    "post_id": "1xiozmn",
    "summary": "A building automation technician reports configuration and lag difficulties interfacing Johnson Controls PCG1610 controllers with new 2-10VDC modulating valves.",
    "category": "features",
    "comments": [
      {
        "url": "https://www.reddit.com/r/BuildingAutomation/comments/1xiozmn/comment/19ru8muf8z63p/",
        "depth": 0,
        "score": 3,
        "author": "hhhhnnngg",
        "excerpt": "Are you changing the Min Value or Min Output Value? It needs to be Min Output Value to scale it properly if I recall correctly",
        "posted_at": "2026-10-29T16:55:40.000Z",
        "author_url": "https://www.reddit.com/user/hhhhnnngg/"
      },
      {
        "url": "https://www.reddit.com/r/BuildingAutomation/comments/1xiozmn/comment/19rui6vkysomb/",
        "depth": 0,
        "score": 3,
        "author": "Disastrous-Lemon8276",
        "excerpt": "It can be changed in PCT. I can post a picture later if that helps",
        "posted_at": "2026-10-29T20:29:56.000Z",
        "author_url": "https://www.reddit.com/user/Disastrous-Lemon8276/"
      },
      {
        "url": "https://www.reddit.com/r/BuildingAutomation/comments/1xiozmn/comment/19ruhqzqxuu8z/",
        "depth": 0,
        "score": 3,
        "author": "Battlewaxxe",
        "excerpt": "there is definitely an option to change it to 2-10 in pct/cct, probably a way to get to it in mct, and definitely with mel if you can bring it back from the dead with .net framework workarounds.",
        "posted_at": "2026-10-29T20:20:02.000Z",
        "author_url": "https://www.reddit.com/user/Battlewaxxe/"
      },
      {
        "url": "https://www.reddit.com/r/BuildingAutomation/comments/1xiozmn/comment/19ru8x3bgn6oz/",
        "depth": 0,
        "score": 2,
        "author": "JREControls",
        "excerpt": "Are they Belimo -MFT actuators? If so, you can program them for 0–10VDC using the Belimo ZTH programmer. Also, it sounds like you have access to CCT? If so, you can open the .caf file and adjust the hardware output range from 0–100% to 20–100%. It sounds like you already tried something similar by setting the minimum to 19%, which is the right idea. Just make sure you're making that adjustment in",
        "posted_at": "2026-10-29T17:02:03.000Z",
        "author_url": "https://www.reddit.com/user/JREControls/"
      },
      {
        "url": "https://www.reddit.com/r/BuildingAutomation/comments/1xiozmn/comment/19ruusjj8yn4z/",
        "depth": 0,
        "score": 2,
        "author": "cbytes1001",
        "excerpt": "You should have 2-10, but also you can setup a scale with 20 as the low output and 100 as the high output.",
        "posted_at": "2026-10-30T01:12:28.000Z",
        "author_url": "https://www.reddit.com/user/cbytes1001/"
      },
      {
        "url": "https://www.reddit.com/r/BuildingAutomation/comments/1xiozmn/comment/19rufxeg431d1/",
        "depth": 0,
        "score": 1,
        "author": "entensiv_controls",
        "excerpt": "Can you put a span block in between the loop outout and the hardware output. 0-100 -> 20-100",
        "posted_at": "2026-10-29T19:39:11.000Z",
        "author_url": "https://www.reddit.com/user/entensiv_controls/"
      },
      {
        "url": "https://www.reddit.com/r/BuildingAutomation/comments/1xiozmn/comment/19rv74603m6jo/",
        "depth": 0,
        "score": 1,
        "author": "gadhalund",
        "excerpt": "Change it in cct. Engineering values or hardware values. Make 0->2",
        "posted_at": "2026-10-30T05:48:45.000Z",
        "author_url": "https://www.reddit.com/user/gadhalund/"
      }
    ],
    "evidence": [
      "[post] I have a site with several PCG1610 controllers, utilizing analog modulating valves for the heating and cooling. Recently, all of the valves were changed out with new Belimo valves and operators.",
      "[post] The problem experienced, is the original valves were 0-10vdc, while the new valves are 2-10vdc. This is causing lag issues when calls for heating and cooling are placed. There is no option for 2-10vdc in the setup"
    ],
    "virality": "medium",
    "post_date": "2026-10-29T16:36:59.000Z",
    "post_kind": "text",
    "post_text": "Greetings!\n\nI have a site with several PCG1610 controllers, utilizing analog modulating valves for the heating and cooling. Recently, all of the valves were changed out with new Belimo valves and operators. The problem experienced, is the original valves were 0-10vdc, while the new valves are 2-10vdc. This is causing lag issues when calls for heating and cooling are placed. There is no option for 2-10vdc in the setup, and modifying the output for 19% minimum out does not help, it does not increase above 2vdc until the call exceeds 25%. Has anyone run into this before, and if so, what did you do to work around it?\n\nThanks, appreciate any and all assistance!",
    "sentiment": "negative",
    "subreddit": "BuildingAutomation",
    "event_date": "2026-10",
    "post_title": "JCI PCG Controllers Question",
    "prominence": "core",
    "source_url": "https://www.reddit.com/r/BuildingAutomation/comments/1xiozmn/jci_pcg_controllers_question/",
    "entity_role": "vendor",
    "post_author": "Zerobeat50125",
    "upvote_ratio": 1,
    "mention_count": 3,
    "mention_surge": true,
    "subreddit_url": "https://www.reddit.com/r/BuildingAutomation/",
    "total_upvotes": 3,
    "comments_total": 21,
    "total_comments": 21,
    "event_date_text": "Recently",
    "other_companies": [
      {
        "name": "Belimo",
        "role": "partner",
        "domain": "belimo.com"
      }
    ],
    "post_author_url": "https://www.reddit.com/user/Zerobeat50125/",
    "signal_category": "feedback",
    "comments_included": 7,
    "products_mentioned": [
      "PCG1610",
      "CCT",
      "PCT"
    ]
  }
}

Long text fields are shortened on this page.

Looking up one signal by its id is free. Enrich costs 2 credits per signal returned; a call with no results is free.